![]() |
![]() |
![]() |
|
![]() |
Attachment 1: Locations Used For Transfilling of Liquid
Oxygen
August, 2004 Information Bulletin 04-15 Use Of Liquid OxygenPurpose:The use of liquid oxygen in health care facilities has increased dramatically in the past few years. This Information Bulletin outlines the basic requirements of National Fire Protection Association Standard 99 (NFPA 99) for the safe storage, transfer and use of liquid oxygen in a health care facility. The 1999 edition of NFPA 99 is adopted by reference in the 2000 edition of NFPA Standard 101 ( Life Safety Code ). Background:Transferring (also referred to as transfilling) of liquid oxygen
from one container to another presents several potential hazards, which include
the:
Here are some important elements to remember relating to the storage and use of liquid oxygen:
Here are two other points to be aware of relating to the temperature and vaporization hazards:
Frequently Asked Questions:What is considered storage and what is considered use? A single base container, or multiple manifolded containers, of liquid oxygen that is assigned to a specific resident, is providing oxygen to the resident through a physical connection, or is ready to provide oxygen to the resident through a physical connection is considered in use in that resident's bedroom. It is acceptable to have one base container or a manifold of containers and one small (2-liter) portable container assigned to the same resident concurrently in the bedroom. It is also acceptable to have a base container or manifold of containers assigned to each resident in a multi-bed room. Each of these residents may also have a portable container in their bedroom. If using a manifold of containers, the facility must be able to provide a physician's order supporting the need for multiple containers to meet the prescribed administration rate. Additional base containers or small portable containers assigned to a resident and kept in that same resident's bedroom are considered to be in storage . Base containers or small portable containers that are not connected to a resident and are placed in the means of egress, common spaces, nurse station or other rooms within the facility are considered to be in storage . How many cubic feet are in a liter of liquid oxygen? Base containers for liquid oxygen are available in several capacities. Base containers are commonly 31 or 41 liters in capacity. A liter of liquid oxygen at 70 degrees Fahrenheit and 14.7 pounds per square inch (psia) is equal to 30.4 cubic feet of gaseous oxygen. Using this conversion factor, multiply the number of liters in the base container of liquid oxygen by 30.4. The resulting product is the number of equivalent cubic feet of oxygen. For example, 41 liters of liquid oxygen times 30.4 equals 1246.4 cubic feet of oxygen. A 41-liter base container is equivalent to 1246.4 cubic feet of oxygen at standard pressure and temperature. Storage:The storage of nonflammable gases is addressed in NFPA 99, Sec. 8-3.1.11. Storage requirements are divided into two categories - requirements for quantities less than 3000 cubic feet and requirements for quantities more than 3000 cubic feet. Using the conversion factors outlined earlier, it follows that three (3) 41-liter containers of liquid oxygen in storage exceeds the threshold 3000 cubic feet. Here are some important points to remember about the storage of liquid oxygen: Storage of liquid oxygen that is less than the equivalent of 3000 cubic feet: The requirements for storage of nonflammable gases in quantities less than 3000 cubic feet can be found in NFPA 99, Sec. 8-3.1.11.2. Indoor storage is required to be in a locked enclosure and properly separated from combustible or incompatible materials. Sources of ignition are prohibited within the storage location and oxygen cannot be stored with any flammable gas, liquid or vapor. Sec. 8-3.1.11.2 also makes references to a number of other sections of NFPA 99. Storage of liquid oxygen that is more than the equivalent of 3000 cubic feet: The requirements for storage of nonflammable gases in quantities greater than 3000 cubic feet can be found in NFPA 99, Sec. 8-3.1.11.1, which requires compliance with Sections 4-3.1.1.2 and 4-3.5.2.2 of NFPA 99. In addition to the requirements outlined in the previous paragraph, such storage locations must be enclosed with construction providing a fire-resistance rating of at least one hour. Such locations shall also be vented to the outside by a dedicated mechanical ventilation system (natural ventilation is allowed where the storage location has at least one exterior wall). Transferring Liquid Oxygen From One Container To Another:NFPA 99, Sec. 8-6.2.5.2 addresses the transferring liquid oxygen from one container to another. This section specifically addresses where transferring can occur within a facility, but references two Compressed Gas Association (CGA) Pamphlets for the types of equipment allowed to be utilized for transferring and for the use and operation of small portable liquid oxygen systems. Although the CGA pamphlets also address where transferring can occur, the Centers for Medicare and Medicaid Services (CMS) has determined that the location requirements of NFPA 99, 8-6.2.5.2 take precedent. Sec. 8-6.2.5.2 makes no distinction in the size (capacity) of either the donating or receiving container. Therefore, these requirements are applicable whether transferring liquid oxygen from one base container to another or from a base container to a 2-liter portable container. Sec. 8-6.2.5.2 requires that the transferring of liquid oxygen from one container to another inside the facility be accomplished in a room specifically designated for the transferring. Refer to attachment #1 at the end of this Information Bulletin for specific requirements for this room. Sec. 8-6.2.5.2 specifies that:
The 2000 edition of CGA Pamphlet P-2.7 refers to transferring of liquid oxygen as “transfilling”. This Pamphlet provides further guidance regarding transferring. Sec. 5.2.1 states that: “An oxygen-enriched atmosphere constitutes a potential fire hazard. Filling of base unit oxygen containers should be performed only in an area outside the facility that is as large and open as possible. An active ventilation system will also help to lessen oxygen buildup. Filling performed inside a building should be limited to the portable unit only. Areas used to exit the building should not be used for filling or storage of liquid oxygen systems.” Sec. 5.3 of that pamphlet states: “Because the atmosphere may become oxygen enriched by venting of the containers during filling, use, or storage, it is important to remove sources of ignition from the immediate area. Filling and use should occur a minimum of 5 feet away from electrical appliances. Cigarettes, cigars, pipes, matches, cigarette lighters, candles, fireplaces, and other sources of open flame must not be used in the same room where liquid oxygen systems are filled, stored, or used.” Conclusion:It is very important that transferring of liquid oxygen be performed only by properly trained and qualified persons who are familiar with the precautions necessary to avoid the hazards listed previously. It is equally important that the oxygen vendor provide written operating instructions for the safe transfer of liquid oxygen and that those instructions be carefully followed. The new Life Safety Code survey documents specifically address the requirements for transferring liquid oxygen from one container to another at tag K-143. The safe use and storage of liquid oxygen are addressed at tag K-076. Deficiencies will be issued if the requirements of NFPA 99 are not met. The Department strongly recommends that a facility that is considering the use of liquid oxygen review and become familiar with all of the applicable requirements of NFPA 99 (1999 edition). Although attachment #1 details the major requirements for a liquid oxygen transfer room, facilities are encouraged to obtain a copy of the standard in order to become familiar with all the requirements that are applicable to certified health care facilities. Further, the facility should identify a room or rooms that comply with the aforementioned requirements for transferring liquid oxygen. Copies of NFPA 99 (1999 edition) are available from the National Fire Protection Association in Massachusetts. The NFPA can be reached at 1-800-344-3555. Copies of the CGA pamphlets are available from the Compressed Gas Association in Virginia. The CGA can be reached at 703-788-2700. It is our understanding that you must be a member of CGA to purchase these pamphlets. This information bulletin was authored by the Minnesota Department of Health, Compliance Monitoring Division, and the Minnesota Department of Public Safety, State Fire Marshal Division. If you have any questions about this information bulletin, please contact either Mr. James P. Loveland, Engineering Program Manager, at 651-201-3710 or Mr. Robert L. Imholte, Deputy State Fire Marshal Supervisor, at 320-685-8559. Mr. Loveland's email address is jim.loveland@health.state.mn.us . Mr. Imholte's email address is bob.imholte@state.mn.us . Attachment #1: Locations Used For Transfilling of Liquid OxygenThis attachment outlines the major requirements that apply to rooms used for the transfer of liquid oxygen from one container to another. The contents herein are based on provisions found in Chapters 4 and 8 of the 1999 edition of NFPA 99 and Chapters 27, 30 and 32 of the 2003 Minnesota State Fire Code.
For questions about this page, please contact our Minnesota Health Care Facilities Programs: health.fpc-web@state.mn.us See also > Division of Compliance Monitoring Home Page |
||||